Product info
- CE marked according to standard EN 15650:2010.
- The fire classification of the fire damper is EI 60 (ve,ho,io) S and in a concrete slab additionally E 90 (ho,io) S
- Approved for installation in compartmenting brick, concrete and plasterboard walls and concrete slabs.
- The fire damper can be installed in the wall with the damper blade axis in either the horizontal or vertical position.
- Manufactured in accordance with the ISO 9001 quality management system.
- External quality control is the responsibility of Eurofins Expert Services Oy
- Can be installed in circular 100 to 630 mm ventilation ducts.
- Damper tightness Class 4, EN1751
- Duct tightness Class C, EN 1751.
- Suitable for use in ducts with a maximum pressure of 3300 Pa.
- Closing tests have been carried out on the fire damper at a duct velocity of 15 m/s
- Equipped with an electric or mechanical actuator